YouTube Video - Paragon HVAC - HMI Addressing and Configuration

YouTube Video - Paragon HVAC - HMI Addressing and Configuration

Video Transcript
0:00
in this video we are going to be
0:01
discussing addresses and configurations
0:03
of the hmis we will access this menu by
0:06
pressing the bottom two button
0:08
simultaneously notice the menu now
0:10
displayed is titled configuration this
0:12
is the specific Hardware configuration
0:14
for this local HMI we discussed in an
0:16
earlier video that the Paragon hpac can
0:19
have up to five total hmis one will
0:21
always be mounted in the unit with up to
0:23
four additional ones in the space the
0:26
HMI modbus addresses will be as follows
0:28
55 56 57 58 and 59 where 55 is always
0:34
the unit mounted HMI with each
0:35
additional one being a space HMI if
0:38
configured as such at a minimum the unit
0:40
will always have one unit mounted HMI
0:43
addressed as 55 if a change is made in
0:46
the communication section you will be
0:47
prompted to save this change as you
0:49
click menu to back out the b rate and
0:52
parity should be always set to a default
0:54
of
0:55
115200 and even as default it is not
0:59
uncommon for space hmis to get missed
1:01
during the installation process so this
1:03
should be verified once installation is
1:05
complete if a unit is configured to have
1:07
three hmis and after applying power to
1:09
it it displays an HMI com 3 fault there
1:12
is a good chance the space HMI that
1:14
should be addressed as 57 is either not
1:16
installed or not addressed accurately
1:19
the advanced options and Status menu
1:21
should only be used for in-depth
1:23
Diagnostics by trained technicians in
1:25
these menus you can view realtime
1:27
temperatures relative humidities uptime
1:29
and HMI data as well as assign offsets
1:32
to those values to further tune that HMI
1:34
precise control over space conditions