YouTube Video - Paragon HVAC - Construction Mode

YouTube Video - Paragon HVAC - Construction Mode


Video Transcript
0:00
in this video we will be discussing
0:02
construction mode construction mode is a
0:04
factory setting for temperature control
0:06
in an unfinished building it allows for
0:08
all Factory programming for designed
0:10
applications to be overridden for unit
0:11
function in the space one of the last
0:14
steps in construction is Plastering
0:16
drywall and paint also more times than
0:18
not all the wiring and controls have not
0:20
been set up during this time the
0:22
building needs to maintain ideal Heating
0:24
and Cooling tolerances so that the
0:25
plaster drywall and paint can dry
0:28
properly another byproduct of
0:30
construction is poor indoor air quality
0:31
by builtup debris in the air to prevent
0:34
debris from entering the Paragon HVAC
0:36
construction mode forces the unit
0:38
temporarily into a 100% outdoor Air
0:41
configuration construction mode will use
0:43
discharge tempering to Target a precise
0:45
discharge temperature and intake
0:47
activation for a call of either heating
0:49
or cooling the blower mode will be set
0:51
to manual allowing for an onoff function
0:54
the unit mounted HMI will be the only
0:56
one in use supply duct adjust is forced
0:59
off and CO2 override and CO2 threshold
1:02
are disabled while construction mode is
1:04
enabled
1:05
on each unit will be shipped with
1:07
construction mode enabled and will be
1:09
disabled during
1:10
stdv once construction mode is exited
1:12
all unit operations will be restored to
1:14