in this video we will be discussing
construction mode construction mode is a
factory setting for temperature control
in an unfinished building it allows for
all Factory programming for designed
applications to be overridden for unit
function in the space one of the last
steps in construction is Plastering
drywall and paint also more times than
not all the wiring and controls have not
been set up during this time the
building needs to maintain ideal Heating
and Cooling tolerances so that the
plaster drywall and paint can dry
properly another byproduct of
construction is poor indoor air quality
by builtup debris in the air to prevent
debris from entering the Paragon HVAC
construction mode forces the unit
temporarily into a 100% outdoor Air
configuration construction mode will use
discharge tempering to Target a precise
discharge temperature and intake
activation for a call of either heating
or cooling the blower mode will be set
to manual allowing for an onoff function
the unit mounted HMI will be the only
one in use supply duct adjust is forced
off and CO2 override and CO2 threshold
are disabled while construction mode is
on each unit will be shipped with
construction mode enabled and will be
stdv once construction mode is exited
all unit operations will be restored to