welcome everybody to another service
today i'm going to talk about the modbus
network that we use here in our control
we're going to talk about what it is how
it works and some common faults that we
see here in the tech support team
be sure to follow all safe work
practices especially the use of ppe
all circuits should be de-energized
prior to any wiring or service
remember many of our controls will have
more than one circuit that will need to
be turned off after de-energizing the
verify that the circuit is dead then
lock out and tag the breaker
first let me explain what a modbus
network is a modbus network is an
internal device network where you have
several devices all connected together
daisy chained together with cat5 cable
so for example we have three vfds so
because they're all daisy chained
on one network with one single cable
each device has to have its own unique
so for example we have two exhaust fans
the two exhaust fan address will be 11
supply fan addresses start at 21 and
then all the other devices on the
hmis core panels filter monitors
each device is going to have to have a
unique address to all work on this
network so every modbus fault
is a communication problem so one of
three things is going to happen
either the circuit board is looking for
a device it's programmed to look for a
device that doesn't exist in the network
maybe your device is powered down you
haven't plugged it in something like
you have a device that's in a fault
condition that'll cause a modbus fault
or this circuit board controls these
devices it tells these devices what to
if this board is telling this device to
do something that it cannot do
because of an internal limit that'll
just remember that any modbus fault is
about 10 to 20 seconds to show up and
it's going to take just as long to go
so when you're troubleshooting you're
tracking down a modbus fault
you kind of have to work at a slower
pace because the modbus fault you make a
change in the network say you change
this cable you suspect this cable is bad
the fault doesn't go away right away oh
now you're frustrated because well that
just give it a little bit of time give
for the fault to clear itself because
this board is going out and pinging each
device periodically and that's when it
clears and that's when it shows up
so again work at a little bit slower
pace because the faults take a long time
to show up and a long time to go away
so now i'm going to talk about some of
the most common faults that we see
here at tech support especially on new
startups new jobs as soon as you apply
power and vfds are powered up you get
some faults these are the most common
the most common is just a general modbus
fault hmi is going to say modbus fault
and give you a device number you know
vfd number two something like that and
then you have to track it down you have
to figure out where the fault's coming
the most common problem a lot of times
is the vfds aren't powered up
you've powered up the board you've
applied power to the circuit board but
powered up that'll cause a modbus fault
because again it's a communication
the board is looking for a device it
can't see because it doesn't have any
so make sure all your vfds are powered
the other most common problem is after
tested balance you have a test and
he'll set the fan speed we set fan speed
display on the front of the hood through
there are limits inside the vfd and we
do that because we're using direct drive
fans the fan wheels have a
specific maximum rpm that they can't
that rpm is calculated and we put a
limit in the vfd for max speed
well the board doesn't know what that
limit is you can set the board
above that limit so when you do that
and you push the fans button you tell it
to run at high speed you'll get a modbus
and it just says modbus fault exhaust
something like that the problem is is
is asking the vfd to run at a higher
than the vfd is allowed to run that'll
cause a modbus fault and that trips
people up all the time we see it most of
the air balancer is finished the last
common problem that we see
at startup on a new job is when you have
a vfd that's mounted in a fan
so this is our supply fan vfd for
example this could be mounted
in the dedicated makeup air unit on the
in the fan if that's the case
you have to run a cat5 cable from this
up to the roof to the one that's mounted
in the fan that gets missed a lot
and so the guys will turn everything on
and have a modbus fault supply vfd
and that's usually the most common
problem the other common problem we see
is when you make up a cat5 cable in the
field when you're actually making it up
putting the ends on crimping it down
if you get two wires reversed something
like that that'll cause a modbus fault
so get yourself a cheap tester it's
available at all the big box hardware
it's a good little investment to be able
to test that cable after you've done it
the last problem i want to talk about is
problem where you have a vfd that's
the time that we see this and we get
when a vfd has gone bad electrician
service guy has ordered a new vfd
now he has a modbus fault as soon as he
powers it up gets a modbus fault
why am i getting this fault a lot of
times when you order these vfds
if we don't have really good details got
duplicate vfds the factory doesn't know
how to program they don't know what
address to program it for
so a lot of times they'll come out
at address 11 or exhaust fan number one
maybe you replaced exhaust fan number
two so now you have two vfds with the
that's going to cause a modbus fault so
if you suspect that it's an address
problem contact the tech support team
for help on changing the address it's
kind of a little bit of drawn out
process getting into the vfd
so i recommend that you contact our team
the next modbus fault that i'm going to
talk about is when the device is
actually in a fault condition
some of the most common ones we see
especially at startup brand new jobs
most common is the fault number eight so
everything powered up push fans button
and boom you have an hmi just showing a
fault fault number eight exhaust vfd one
something like that what a fault number
eight is it's an overload fault
it just simply means that the motor just
pulled too many amps it's like an old
you know mechanical overload so you have
to troubleshoot the motor
why it's pulling too many amps it could
be that the rotation is backwards
that's the most common problem is
backwards rotation remember you have to
check the rotation on the fans visually
you can't just test that it's moving air
in the right direction they'll move air
in the right direction even when they're
running backwards but they pull really
the next problem could be that you have
the wrong fan on the wrong vfd
so say you have two fans you have a one
horsepower motor and a two horsepower
you put the two horsepower motor on the
one horsepower vfd that'll cause them
because you can't run a larger motor
than the vfd is rated for
the next most common problem that we see
fault number eight but it's fault number
three number three is a ground fault
to track down a ground fault there's a
few steps that will help you kind of
narrow down where the ground fault was
ground fault is simply just a short to
ground a direct short to ground
between the vfd and the motor it's
so we suggest you watch our video on
troubleshooting ground faults it's going
to give you a lot more detail on how to
troubleshoot narrow down where that
so you're not having to look through the
entire circuit the last two most common
maybe not so much as startup but you
know after long term is a fault number
and a fault number seven fault number
is a temperature fault that simply means
that the drive itself is getting too hot
and it will shut down and give you a
show you display a fault number four on
things to look for is some of these
drives the bigger drives and three
horsepower or larger i believe
they get an internal cooling fan so make
the other thing to check is make sure
this cooling fan the cabinet fan is
that the filter on top is clear you
don't have any paper sitting up here
no dust anything like that and lastly
cabinet vents are clear so that you're
getting good airflow through this
cabinet to keep those drives
cool and then the last fault we'll talk
about is the fault number seven
number seven is uh low dc bus voltage we
a lot and it mainly comes after
say there's a thunderstorm that rolls
through the area and the restaurant
experiences a power failure in the
middle of dinner service for example
when the system comes back up a lot of
times they'll show us fault number seven
and it's a low dc bus voltage it's an
internal fault to the drive
all it simply means is that the line
dropped below a certain point which is
exactly what it did when the power went
out so to clear the fault
all you have to do is cycle power to the
drive at the breaker panel
so you turn the breaker off wait for
as soon as it goes blank you can turn
the breaker panel back on
this drive will reset and you should be
good to go that should solve this fault
number seven so there are other devices
and situations that can cause a modbus
fault but just remember a modbus fault
is always a communication fault
so the troubleshooting is going to be
basically the same if you have any
questions on this or any of our products
feel free to contact our tech support