Fans and Ventilators Videos

Fans and Ventilators Videos

RTC Fan Speed Controller
Video Transcript
0:00
hello John elder again with another
0:01
video in our component series this video
0:04
will cover the RTC fan speed controller
0:07
that we use on some of our fans with EC
0:10
motors I will cover standard operations
0:12
and programming of the controller let's
0:15
start by looking at the speed controller
0:16
itself upon powerup the controller will
0:19
display the letter P and a number which
0:21
is the speed setting the speed setting
0:23
is a percentage from zero to a hundred
0:25
so in this example my controller is
0:27
showing P 90 so the motor would run at
0:30
90 percent once the motor has started
0:33
the display will flash back and forth
0:35
between the setpoint and the motor rpms
0:38
if your display flashes between the
0:40
setpoint and off it means the controller
0:43
is not receiving a feedback signal from
0:45
the motor for rpms so it thinks the
0:48
motor is stopped the controller will
0:50
however continue to send an output speed
0:53
signal and run the motor even though
0:54
it's not receiving the feedback looking
0:57
at the back of the controller you can
0:58
see that their input terminals for 24
1:01
volts AC to power the controller a 0 to
1:04
10 volt DC output terminal a ground
1:07
terminal and a 0 to 10 volt DC input
1:10
terminal there are also two plugs one
1:13
for use with an eye Dec motor and one
1:15
for telco motors care should be taken to
1:18
ensure that these plugs get plugged in
1:20
correctly if they're plugged in upside
1:22
down the motors will not run now let's
1:25
cover programming navigating the
1:27
programming is very simple push and hold
1:29
the center button on the controller
1:31
until the display changes then up or
1:33
down buttons to cycle through the
1:35
available menus and left and right
1:37
buttons to enter and exit a menu to
1:40
change a menu setting after entering the
1:43
up and down buttons will cycle through
1:44
your options and your option will be
1:47
saved when you press the left button to
1:49
exit the menu once programming is
1:51
complete just leave the controller alone
1:53
for several seconds and it will return
1:55
to normal operations with the new
1:57
settings now I'm going to take a closer
1:59
look at each menu the first menu is a PP
2:02
or application the options are F SC fan
2:07
speed control where the motor is plugged
2:09
directly into the speed controller or 0
2:12
to 10
2:12
which is a zero to 10 volt DC output
2:15
which would make the speed controller
2:17
send out a zero to 10 volt DC output
2:19
signal to be used to control a motor
2:22
remotely remember the left button will
2:25
exit a menu you have entered allowing
2:27
you to move on to the next menu the next
2:31
menu is SP which stands for setpoint
2:33
this is the speed setting that the motor
2:35
will run at the setting is a percentage
2:37
from zero to 100% so a setting of
2:40
setpoint of 50 would cause the motor to
2:42
run at half speed if all you need to do
2:45
is change the speed you can also just
2:47
push the up or down buttons without
2:49
entering the programming and change the
2:51
speed then the center button to save it
2:53
the next menu is LSPD or low speed limit
2:57
setting this to 20 for example will not
2:59
let you run the motor slower than 20%
3:02
just like low speed the next menu HS PD
3:06
is high speed and works the same way the
3:09
next menu is typ or type
3:11
this tells the controller what brand and
3:13
type of motor you're trying to control
3:15
your options here are n ID for nigh Dec
3:19
motors or TC 42 for a telco model 42
3:23
motor or TC 48 for a model 48 motor the
3:28
telco model numbers can be found on the
3:30
motor label the next menu is re this
3:33
stands for a remote your options here
3:35
are to enable or disable which will turn
3:38
on or off the 0 to 10 volt DC input
3:41
terminal if enabled the motor speed will
3:44
be controlled by the signal not the
3:46
speed setpoint this allows the speed
3:49
controller to receive a 0 to 10 volt DC
3:51
input signal which will in turn control
3:54
the motor speed so if the controller
3:56
received 5 volts DC on the input
3:59
terminal the motor would run at 50
4:01
percent of Max the last menu is V er
4:05
which stands for version this only
4:07
displays the software version the speed
4:09
controller is programmed with there are
4:11
no changes in this menu
4:13
for more information or questions you
4:15
can call one eight six six seven eight
4:17
four sixty nine hundred or email support
4:20
at cast service calm


Exhaust and Supply Fan Motor Controls
 
Video Transcript
0:01
hello everyone john elder again with
0:03
another service video this one's going
0:04
to cover all the ways we control our fan
0:06
motors

Safety

0:08
be sure to follow all safe work
0:09
practices especially the use of ppe
0:12
all circuits should be de-energized
0:13
prior to any wiring or service
0:15
remember many of our controls will have
0:17
more than one circuit that will need to
0:19
be turned off
0:19
after de-energizing the circuit verify
0:22
that the circuit is dead
0:23
then lock out and tag the breaker

Motor Control Options

0:27
first let's talk about a belt drive fan
0:29
these fans have been around for years
0:31
and have been kind of industry standard
0:33
for a lot of years these fans are
0:35
typically controlled by a contactor
0:36
that when energized will send full
0:38
voltage to the motor the motor runs at
0:40
full speed
0:41
so the only way to control the fan speed
0:43
is to either adjust the
0:45
motor pulley or the fan pulley
0:48
or changing the pulleys out to a
0:50
different combination the next way we
0:52
control a fan motor is with a vfd or a
0:54
variable frequency drive
0:55
what these drives do is they take in
0:57
constant power at constant frequency
1:00
and then they convert that power and
1:02
change the frequency to the motor and
1:04
that's what controls the speed of the
1:05
motor
1:06
most of these fans are going to be
1:07
direct drive fans with three-phase
1:09
motors in them
1:10
so really with a vfd is the only way you
1:12
can control fan speed because you have
1:14
no pulleys or
1:15
anything to control them with in certain
1:17
conditions the vfd can either be mounted
1:19
in the fan
1:20
it can be mounted inside the building on
1:22
a wall somewhere or it can be mounted in
1:24
the hood control package
1:26
either way the vfd has to be protected
1:28
from the weather
1:29
and it has to be mounted in a well
1:30
ventilated place because those vfds
1:32
build up a lot of heat
1:33
the vfd can be controlled in a couple of
1:35
different ways first is it can be set up
1:37
to just run at a constant speed whenever
1:39
power is applied
1:41
second is it can receive a remote signal
1:43
from like a modbus network or from a
1:45
building management system for example
1:47
be sure to check your wiring diagram for
1:49
your job to see which type of control
1:51
you're using

Electronically Commutated Motors

1:52
the rest of our motor control involves a
1:54
totally unique type of motor that we use
1:56
here
1:56
it's an ec motor it's an electrically
1:59
commutated motor
2:01
all the electronics for that motor that
2:02
it needs to run
2:04
are contained within the motor so that
2:06
motor gets voltage applied to it high
2:09
voltage applied to it
2:10
from the breaker panel so it's standing
2:12
power and in order to get that motor to
2:14
run it has to receive a pwm
2:16
signal or pulse width modulation signal
2:19
that could be generated in a couple of
2:20
different ways we have a speed
2:22
controller that can generate that pulse
2:24
width modulation
2:25
we can also do it through one of our
2:27
control packages first is our control
2:29
panel
2:30
so if you wire the low voltage wiring
2:32
from the fan
2:34
with a twisted shielded pair down to our
2:35
control package
2:37
you wire that fan to the correct p
2:38
terminals on the control package
2:40
ensuring that the polarity is correct
2:43
our control board will
2:45
produce that pwm signal and control the
2:47
fan start as well as a fan speed
2:50
we also have a separate ec motor
2:52
controller
2:53
that just like a vfd can be set up to
2:55
run at a set speed or receive a remote
2:57
signal
2:58
we have a video specifically just for
3:00
motor controls and ec
3:02
motors so be sure to check that one out

Closing

3:04
remember that every job is custom built
3:06
so there's no two jobs alike
3:08
the wiring diagram on your job site is
3:10
critical to making sure that everything
3:12
gets wired and functions properly
3:14
if you have any questions about this or
3:15
any of our products feel free to call or
3:17
email
3:18
thanks for watching


Power Pack Replacement